Fans P2173HBT-ETS 230V AC axial fan 17238
A 230 V AC axial fan delivering 348 to 390 m³/h airflow at 2750 to 3150 rpm for UPS or industrial cooling
- Runs on 230 VAC mains supply without extra power conversion
- Delivers up to 390 m³/h airflow for strong case cooling
- Operates from -10 °C to +70 °C for harsh environments
- Terminal connectors with 110 mm pins simplify installation
- Rated for 20000 hours life expectancy in normal use
AC axial fan for UPS and industrial cooling
The P2173HBT-ETS is a 230 V AC axial fan built for high-temperature environments such as UPS units and industrial enclosures. It operates across a 200–250 V AC range with a starting voltage of 150 V AC, making it suitable for equipment that runs directly from mains power.
Airflow and noise at two rated speeds
At 50 Hz the fan spins at 2750 rpm, delivering 348 m³/h at 0.53 in-H₂O static pressure and 54 dB noise. At 60 Hz it reaches 3150 rpm, moving 390 m³/h at 0.59 in-H₂O and 58 dB. Power draw stays at 24 W in both cases, with current at 0.10 A or 0.11 A respectively.
Terminal connection and bearing life
The unit uses 2-pin 110 male terminals on 22 AWG leads for direct wiring without a plug. A ball bearing system supports a 20000-hour life expectancy in normal use across an operating range of -10 °C to +70 °C. The 800 g frame is designed for fixed mounting in rack or cabinet installations.
How it compares
Measured against everything we stock in PC Cooling Fans, at today’s prices. Recalculated every night.
- Price $42.99
- Pricier than about 86% of the 8,339 comparable items (median $19.99).
New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.
Specifications
No published specifications for this item yet.
Questions about this item
How do I choose between the 50 Hz and 60 Hz airflow figures?
At 50 Hz the fan delivers 348 m³/h at 2750 rpm; at 60 Hz it delivers 390 m³/h at 3150 rpm. Pick the row that matches your local mains frequency.
What does the 24 W power rating mean for my UPS enclosure?
The fan draws 0.10 A at 50 Hz or 0.11 A at 60 Hz, consuming 24 W in either case — size your UPS cooling budget accordingly.
What does the 110-style terminal connection cap in practice?
The 3 mm 2-pin 110 male terminals accept 22 AWG wires and are rated for the fan's 0.10–0.11 A operating current.