Fans R4D560-AW03-01 560mm Centrifugal Blower
Centrifugal blower with 560 mm impeller delivering up to 35000 m³/h airflow at 1365 min⁻¹, 2380 W three-phase motor for 230/400 VAC supplies, operating from -40 °C to 60 °C
- Delivers up to 35000 m³/h airflow for large purification systems
- Operates on 230 V or 400 V three-phase power at 50 Hz
- External rotor motor design provides compact construction and forced electronic cooling
- Speed fully controllable up to 100 % via analogue signal
- Withstands ambient temperatures from -40 °C to 60 °C for harsh environments
560mm Centrifugal Blower for Industrial HVAC
The Fans R4D560-AW03-01 is a new centrifugal blower with a 560mm diameter designed for large purification and air-conditioning systems. It uses an external rotor motor for compact integration and forced electronic cooling. Air flow reaches up to 35000m3/h for demanding ventilation requirements.
Suits three-phase 230/400VAC installations only
This blower suits facilities running three-phase 230VAC or 400VAC at 50Hz with Y-connection wiring. It is not for single-phase residential supplies or DC voltage systems. Buyers needing variable speed without analogue control or lower starting current should look at something else.
Dual-voltage motor runs at 1365 RPM on both 230V
The M4D138-LA motor delivers 1365 min-1 at 2380W whether connected to 230VAC drawing 8.65A or 400VAC drawing 5.0A. Starting current reaches 47A at 230V and 27A at 400V. Maximum safe operating speed is 1640 min-1 across the -40°C to 60°C ambient range.
How it compares
Measured against everything we stock in Air Blowers & Movers, at today’s prices. Recalculated every night.
- Price $1,041.99
- Pricier than about 91% of the 322 comparable items (median $143.49).
Specifications
No published specifications for this item yet.
Questions about this item
What duct or housing diameter does the 560 mm impeller require?
The 560 mm impeller is a free-wheeling backward-curved design that does not require a scroll housing; mount it with adequate clearance for unrestricted airflow.
How do I wire the three-phase motor for 230 VAC or 400 VAC at 50 Hz?
Connect the motor in the Y configuration shown on the nameplate; 230 VAC draws 8.65 A and 400 VAC draws 5.0 A, both at 1365 min-1.
When should I expect to replace the bearings given the -40 °C to 60 °C operating range?
The external-rotor motor is cooled by the airstream; bearing life varies with load and environment, so inspect at regular service intervals rather than a fixed schedule.