Tripp Lite PDUMH30HV PDU 5.8 kW 30A 208/240V 16 C13 2 C19 L6-30P 12ft 2U
A metered 2U rack PDU delivering 5.8 kW at 208/240 V with 16 C13 and 2 C19 outlets, dual 20 A breakers, and built-in current meters on a 12 ft L6-30P cord
- Rack height2U
- Certified standardsTested to UL 60950-1 (USA), CSA (Canada), Class A (Emissions
- Package includes2U rack PDU Mounting brackets Plug retention plates User man
- Supply voltage200 / 208 / 240 V
- Input current rating30A
- Input connectionNEMA L6-30P
- Metered display shows real-time load per bank for balanced power management
- 18 outlets (16 C13 and 2 C19) support dense rack equipment
- Two 20 A breakers protect each 9-outlet bank from overloads
- 12 ft attached cord with NEMA L6-30P plug simplifies installation
- 2U horizontal form factor fits standard 19 in racks
Metered 2U rack PDU
The Tripp Lite PDUMH30HV is a metered power distribution unit that fits a standard 2U horizontal rack space. It accepts a single-phase 208 or 240 volt supply through a NEMA L6-30P plug on a 12 foot cord. The unit delivers power through eighteen locking IEC outlets, sixteen C13 and two C19, for dense server or network deployments.
Continuous load limit
Agency derating restricts continuous current to 24 amps on the 30 amp inlet, yielding a practical ceiling of 5.8 kilowatts at 240 volts. Two 20 amp branch breakers each protect a bank of nine outlets, so no single bank can exceed its breaker rating. The attached meters display real-time amperage per bank to help balance loads and avoid nuisance trips.
Eighteen mixed IEC outlets
Sixteen C13 and two C19 receptacles determine which equipment plugs in directly without adapters. Builders needing more C19 connections or a different inlet type will need another model.
How it compares
Measured against everything we stock in Rackmount PDUs, at today’s prices. Recalculated every night.
- Price $267.99
- Cheaper than about 63% of the 643 comparable items (median $451.99).
New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.
Specifications
| Product | |
|---|---|
| Brand name | Tripp Lite |
| Model name | PDUMH30HV |
| Product type | Metered |
| Design style | Rackmount |
| Power | |
| Supply voltage | 200 / 208 / 240 V |
| Input current rating | 30A |
| Input connection | NEMA L6-30P |
| Voltage output | 200 / 208 / 240 V |
| AC output frequency | 50/60 Hz |
| Output outlets | 16 x C13, 2 x C19 |
| Overload protection | Two 20A breakers protect 9 outlets each |
| Size & build | |
| Rack height | 2U |
| Cord length | 12 ft (3.66 m) |
| Product dimensions | 3.5 in × 17.5 in × 12.5 in |
| Product weight | 13.7 lb (6.21 kg) |
| Shipping weight | 6.90 kg |
| Package size | 511 × 437 × 203 mm |
| In the box | |
| Package includes | 2U rack PDU Mounting brackets Plug retention plates User manual |
| Environment & compliance | |
| Certified standards | Tested to UL 60950-1 (USA), CSA (Canada), Class A (Emissions), NOM (Mexico), RoHS compliant, TAA Compliant |
| RoHS compliance | Yes |
| Operating conditions | -15–50 Celcius degree |
| Operating humidity | 5–95% |
| Operating altitude | 0–10000 ft |
Questions about this item
Should I choose the PDU with 16 C13 and 2 C19 outlets or a different outlet mix?
This model provides exactly 16 IEC C13 outlets and 2 IEC C19 outlets across two load banks of nine outlets each.
What does the 5.8 kW rating mean once the unit is installed in my rack?
The 5.8 kW rating reflects the maximum apparent power at 208/240 V; the agency derating limits continuous draw to 24 A per the dual 20 A breakers.
How does the NEMA L6-30P input plug affect what I can actually draw?
The L6-30P plug connects to a 30 A 208/240 V circuit, but the two 20 A breakers cap each nine-outlet bank at 20 A.