We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

CyberPower

CyberPower PR2000RT2UCN UPS 2000VA 2000W 120V 2U 8 Outlets

SKU CH-MSEW-T9PET MPN PR2000RT2UCN

2U rack-tower UPS delivers 2000 VA and 2000 W sine-wave output through eight NEMA 5-20R outlets with 4.5 minutes runtime at full load

  • Voltage version120 V
  • AC input voltage75–149 VAC
  • Input line frequency47–63 Hz
  • Power inputNEMA 5-20P
  • Volt-ampere rating2000 VA
  • Power rating2000 W
  • Sine-wave output protects sensitive equipment with 2000 W pure sine wave delivery
  • 2U rack/tower form factor fits standard racks or tower placement for flexible deployment
  • Eight NEMA 5-20R outlets provide battery-backed power for multiple critical devices
  • LCD status panel shows real-time voltage, load and battery information at a glance
  • Three-hour recharge restores battery to 90 % capacity for rapid recovery after outages

2000 VA Sine-Wave UPS for Rack

The CyberPower PR2000RT2UCN delivers 2000 VA and 2000 W of pure sine-wave output in a 2U form factor that mounts in a rack or stands as a tower. Eight NEMA 5-20R outlets provide battery-backed surge protection for servers, networking gear and storage arrays. A NEMA 5-20P input plug with a 10 ft cord connects to 120 VAC mains. Line-interactive topology corrects voltage without battery drain.

Line-Interactive Design

The unit accepts an input range of 75 to 149 VAC at 47 to 63 Hz and regulates output to 100, 110, 120 or 125 VAC within five percent. Because the topology is line interactive, the inverter engages only during outages or severe distortion, keeping audible noise low and reducing battery cycles. Sealed lead-acid batteries recharge from zero to ninety percent in three hours. Replaceable battery modules extend service life without replacing the whole chassis.

PowerPanel Business Software

Bundled PowerPanel Business software connects through a serial port to give graceful shutdown, scheduling and event logging across multiple systems. A dry-contact port adds a second path for building-management or SNMP cards to signal battery mode, low battery, overload, overcharge or overheat alarms. Together these interfaces let administrators automate responses without proprietary hardware.

How it compares

Measured against everything we stock in Uninterruptible Power Supplies (UPS), at today’s prices. Recalculated every night.

Price $1,356.99
Pricier than about 61% of the 1,153 comparable items (median $948.99).

New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.

Specifications

Product
Brand nameCyberPower
Product lineSmart App Sinewave UPS Series
Model namePR2000RT2UCN
Ports & slots
Communication ports1 Serial, 1 Dry Contact
Power
Voltage version120 V
AC input voltage75–149 VAC
Input line frequency47–63 Hz
Power inputNEMA 5-20P
Volt-ampere rating2000 VA
Power rating2000 W
Voltage output100/110/120/125 VAC +/- 5%
AC output frequency50/60 Hz +/- 1%
Power outlets8
Battery typeSealed Lead Acid
Runtime on batteryFull Load 4.5 min
Half Load 13.5 min
Battery charge time3 h (0% to 90% charged)
Replacement batteryYes
AlertsBattery Mode
Low Battery
Overload
Overcharge
Overheat
Surge protection rating2430 Joules
Built-in protectionOn Battery: Internal Circuitry Limiting
On Utility: Circuit Breaker Protected
Size & build
Product dimensions17.1 in × 3.4 in × 16.2 in
Product weight59.8 lb (27.1 kg)
Shipping weight30.84 kg
Package size561 × 531 × 274 mm
Software
Control softwarePowerPanel Business

Questions about this item

How do I install the PR2000RT2UCN in a 2U rack and what step is commonly missed?

Mount the 2U chassis using the included brackets, plug the NEMA 5-20P cord into a 20 A branch circuit, then connect the serial or dry-contact cable to your server so PowerPanel Business can trigger graceful shutdowns — the management link is the step most often skipped.

What battery maintenance will the unit need and when?

The sealed lead-acid batteries are user-replaceable; expect to swap them every three to five years, and after a deep discharge allow the three-hour recharge to 90 % before returning to full runtime.

What runtime limit appears first during a prolonged outage at full load?

At 2000 W the battery lasts 4.5 minutes, so the low-battery alarm and automatic shutdown occur long before any thermal or overload limit is reached.

More in Uninterruptible Power Supplies (UPS)