We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

Vertiv

Vertiv GXT5LI-2000LVRT2UXLN 2000VA 1800W 120V UPS

SKU CH-9RRS-D4BQ6 MPN GXT5LI-2000LVRT2UXLN

Lithium-ion UPS delivers 2000VA/1800W with 10.5-minute full-load runtime and sub-two-hour recharge in a 2U rack/tower form factor

  • Voltage version120 V
  • AC input voltage60-150 VAC
  • Power inputNEMA L5-20P
  • Volt-ampere rating2000 VA
  • Power rating1800 W
  • Voltage output120 V; 100/110/115/120 V/125VAC (User-Configurable)
  • Lithium-ion battery recharges to 90% in under 2 hours
  • 9 output power factor delivers 1800W from 2000VA capacity
  • 2U rack/tower form factor fits standard enclosures
  • Seven mixed NEMA outlets support diverse equipment
  • Network card included enables remote monitoring

Product Identity

The Vertiv GXT5LI-2000LVRT2UXLN is a 2000VA/1800W online double-conversion UPS using lithium-ion batteries. It delivers pure sine-wave output at a user-configurable 100/110/115/120/125VAC with a 0.9 output power factor. The unit suits network closets, edge sites and critical workstations that need extended battery life and a compact 2U rack or tower form factor.

Build Integration

The UPS accepts 60-150 VAC input through a NEMA L5-20P plug and provides seven outlets: one L5-20R, two 5-20R and four 5-15/20R receptacles. An included RDU101 network card enables remote monitoring via SNMP or web browser. Hot-swappable battery modules allow replacement without powering down connected loads. The 3.4 x 16.9 x 18.5 inch chassis fits standard 2U rack rails or stands upright as a tower.

Sustained Load Behaviour

At full 1800W load the lithium-ion pack provides 10.5 minutes of runtime; at half load runtime extends to 22.5 minutes. The battery recharges to 90 percent capacity in under two hours. Operating temperature spans 32°F to 104°F with a 10 percent derating at 50°C, while storage tolerates -4°F to 140°F. Surge protection meets ANSI C62.41 Category B for repeated transient events.

How it compares

Measured against everything we stock in Uninterruptible Power Supplies (UPS), at today’s prices. Recalculated every night.

Price $2,686.99
Pricier than about 81% of the 1,153 comparable items (median $948.99).

New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.

Specifications

Product
Brand nameVertiv
Model nameGXT5LI-2000LVRT2UXLN
Power
Voltage version120 V
AC input voltage60-150 VAC
Power inputNEMA L5-20P
Volt-ampere rating2000 VA
Power rating1800 W
Voltage output120 V; 100/110/115/120 V/125VAC (User-Configurable)
AC output frequency40 to 70 Hz
Power outlets7
Battery typeLithium Ion
Runtime on batteryFull-Load Runtime 10.5 min
Half-Load Runtime 22.5 min
Battery charge time< 2hrs to 90%
Size & build
Rack mounting2U Rack/Tower
Product dimensions3.4 in × 16.9 in × 18.5 in
Product weight39.7 lb (18 kg)
Shipping weight24.49 kg
Package size762 × 508 × 508 mm
In the box
In the boxw/RDU101 Network Card Included
Environment & compliance
Regulatory approvalsUL 1642 (Li-Ion Battery Cells), UL 1973 (Li-Ion Battery Pack w/UPS), UL 1778, CSA 22.2 No. 107.3
Temperature rangeOperating Temperature: 32 °F to 104 °F (0 °C to 40 °C) (10% Derating at 50 °C)
Storage Temperature: -4° to 140° (-20° to 60°)
Humidity range0% - 95%, non-condensing
More details
Surge protectionANSI C62.41, Category B

Other versions of this model

5 more in the same range

Questions about this item

How long will the lithium-ion battery run at the full 1800W load before shutting down?

The UPS provides 10.5 minutes of runtime at full 1800W load and 22.5 minutes at half load, with the battery recharging to 90 percent in under two hours.

What are the typical operating temperature limits and does the unit derate above 40°C?

It operates from 0°C to 40°C without derating; at 50°C the output is derated by 10 percent, and storage range is -20°C to 60°C with 0-95 percent non-condensing humidity.

Which input plug and output receptacles are built in so I can match my existing PDU and devices?

The input uses a NEMA L5-20P plug; outputs are one L5-20R, two 5-20R and four 5-15/20R receptacles, all on a 120V single-phase system.