We take cryptocurrency — so the coins you hold can buy real hardware.Pay in crypto, spend it on real hardware. Free insured shipping worldwide over $399. Plain, unbranded boxes, sent from Germany.Free insured shipping over $399. Your rate is locked for 30 minutes once checkout opens.Rate locked 30 minutes. Every item sealed, serial-checked and covered by a 24-month warranty.Sealed, 24-month warranty.

Saved items Sign in

Vertiv

Vertiv PSI5-2200RT120 1920VA/1920W 120V 2U UPS

SKU CH-JYRT-7CGQX MPN PSI5-2200RT120

Line-interactive UPS delivers 1920VA/1920W pure sine-wave output with 0.9 power factor, rotatable LCD, hot-swappable batteries and seven NEMA outlets in a 2U rack/tower form factor

  • Voltage version120 V
  • AC input voltage75-146VAC
  • Input line frequency55 to 65 Hz (57 to 63 Hz Battery to Normal comeback)
  • Power inputNEMA L5-20 std 5-20 adapter included
  • Volt-ampere rating1920 VA
  • Power rating1920 W
  • 9 power factor delivers 1920W real power from 1920VA rating
  • Rotating LCD display gives clear status in both rack and tower orientation
  • Pure sine wave output on battery protects active PFC power supplies
  • 7 outlets including NEMA L5-20R and 5-20R support diverse equipment plugs
  • 1372 joules surge rating shields connected gear from damaging voltage spikes

Power and Capacity

The Vertiv PSI5-2200RT120 delivers 1920VA and 1920W with a 0.9 power factor. Pure sine wave output on battery supports active PFC power supplies in workstations, networking gear and edge devices. Automatic voltage regulation corrects input from 75 to 146VAC without using battery reserves.

Thermals Noise and Runtime

The line-interactive design runs quietly in normal operation while the AVR handles sags and surges. At full load the internal VRLA batteries provide 5.0 minutes of backup; at half load the runtime extends to 14.0 minutes. A 4-hour recharge restores 90 percent capacity for the next event.

Mounting and Connections

The 2U chassis fits rack or tower layouts and the LCD rotates for easy reading in either orientation. Seven outlets include three NEMA 5-15/20R, three NEMA 5-20R and one NEMA L5-20R; a NEMA L5-20 to 5-20 adapter is included. Hot-swappable battery modules allow replacement without powering down connected equipment.

How it compares

Measured against everything we stock in Uninterruptible Power Supplies (UPS), at today’s prices. Recalculated every night.

Price $1,182.99
Pricier than about 57% of the 1,153 comparable items (median $948.99).

New to this? Which coin should you pay with — what to check, what it costs to pay, and what is never asked for.

Specifications

Product
Brand nameLiebert
Product linePSI5
Model namePSI5-2200RT120
Power
Voltage version120 V
AC input voltage75-146VAC
Input line frequency55 to 65 Hz (57 to 63 Hz Battery to Normal comeback)
Power inputNEMA L5-20 std 5-20 adapter included
Volt-ampere rating1920 VA
Power rating1920 W
Voltage output120VAC (100/110/115/125VAC user-configurable)
Power outlets7
Battery typeValve Regulated Lead Acid (VRLA)
Runtime on batteryFull Load: 5.0 min
Half Load: 14.0 min
Battery charge time4 h to recover 90%
Replacement batteryPSI5-72VBATT
Surge protection rating1372 Joules
Size & build
Rack mounting2U Rack/Tower
Product dimensions3.5 in × 17.2 in × 24.8 in
Product weight59.1 lb (26.8 kg)
Shipping weight33.48 kg
Package size780 × 582 × 269 mm
Environment & compliance
Regulatory approvalsUL 1778, c-UL-us Listed
Temperature rangeOperating Temperature: 32°-104 °F (0°-40 °C)
Storage Temperature: 5°-120 °F (-15° - 50 °C)
Humidity range20% to 90% non-condensing

Other versions of this model

5 more in the same range

Questions about this item

How do I install the PSI5-2200RT120 in a 2U rack and what step do people often miss?

Mount the 2U chassis using the included rack ears, connect the NEMA L5-20 input (5-20 adapter supplied), then attach the 7 output receptacles — the step most missed is setting the output voltage to 100, 110, 115 or 125 VAC on the LCD before powering loads.

Which battery module replaces the internal VRLA pack and how often should I plan on swapping it?

Order the PSI5-72VBATT hot-swappable module; typical VRLA life is three to five years, so budget a replacement around the four-year mark and use the rotatable LCD to track battery health.

What is the first limit I will hit if I run the UPS at full 1920 W continuously?

At full load the battery provides only 5.0 minutes of runtime, so the endurance limit appears first — after that the unit needs four hours to recharge to 90 % before it can deliver another cycle.

More in Uninterruptible Power Supplies (UPS)